Ring Main Unit (Air Insulated type)

Fully Air Insulated Ring Main Units are built around the Air Break Load Break Switches of the puffer design. These are available in both extensible and non-extensible types. Being modular in design, they can be factory assembled in any configuration based on application requirements. Bus-bars and HRC Fuses being in Air, make it simple to extend and maintain. Cable boxes are suitable for dry type cable termination of either push fit type or heat shrunk sleeve type. Integral cable earthing facility is provided. Features, such as cable fault location testing access, shunt trip coil for remote tripping, are given as optional items.

Ring Main Unit

All safety interlocks, padlocking arrangements, mechanical status indicators are in place to ensure a high degree of safety level.

 Highest System Voltage   24 KV  12 KV
 System Frequency   50 Hz  50 Hz
 Continuous Current  630 A  630 A
 Short Circuit Breaking    25 kA   25 kA
 Short Circuit making   62.5 kAp   62.5 kAp
 1 min PF withstand (dry)  50kVrms  28kVrms
 Impulse Voltage withstand   125kVp  75kVp
Transformer offload Breaking  16A  16A
Cable  charge Breaking Capacity  25A  25A
Closed Loop Breaking Current  630A  630A
 Weight / panel  650 kg  420 kg